Test the Outputs
Boiler Recirculating Pump (Boil Pmp)
The boiler recirculating pump is connected to the Boil Pmp
terminal (5). Make sure that power to the terminal block is off,
and install a jumper between the Power L and the Boil Pmp
terminals (3 and 5). Install a second jumper between Power N
and N terminals (4 and 6). When power is applied to the Power
L and Power N terminals (3 and 4), the boiler recirculating
pump should start. If the pump does not turn on, check the
wiring between the terminal block and pump, and refer to any
installation or troubleshooting information supplied with the
pump. If the pump operates properly, disconnect the power
and remove the jumpers.
Boiler Enable Contact
If the boiler limit circuit is connected to the Boiler Enable terminals (7 and 8), make sure power to the boiler circuit is off, and
install a jumper between the terminals. When the boiler limit circuit is powered up, the boiler should fire. If the boiler does not
turn on, refer to the installation or troubleshooting information supplied with the boiler. Check for proper operation of each
device in the boiler limit circuit. If the boiler operates properly, disconnect the power and remove the jumper.
Connecting the Control
Make sure all power to the devices and terminal blocks is off, and remove any remaining jumpers from the terminals.
Reconnect the terminal blocks to the control by carefully aligning
them with their respective headers on the control, and then pushing
the terminal blocks into the headers. The terminal blocks should
snap firmly into place.
Install the supplied safety dividers between the unpowered sensor
inputs and the powered or 120 V (ac) wiring chambers.
Apply power to the control. The operation of the control on power up
is described in the Sequence of Operation section of this manual.
4
5
6
Boi
l
Pm
p
Po
we
r
N
3
L
120 V (ac)
Boiler Recirculating
Pump
N
L
N
14
13
15
12
16
Com
Com
Out
Boil
Re
t
Mix
STEP SEVEN
ADJUSTING THE CONTROL SETPOINTS
In order for the RTC to function properly, several control settings must be adjusted. Review the “User Interface” and “Sequence
of Operation” sections of this manual for descriptions of each setting and instructions on how to adjust them. Adjust the follow-
ing settings as specified:
A. ROOM (Room Temperature) – Set the desired room temperature.
B. MIX TARGET This setting can only be used on applications where the mix sensor is installed. When the outdoor reset
feature is not selected, this setting represents the fixed target supply water temperature. On this type of application, the MIX
TARGET setting should be adjusted to match the boiler operating aquastat’s setpoint temperature.
C. MIX DSGN (Mixing Design)When the outdoor reset feature is selected, this setting represents the design system supply
water temperature. If unsure about the original design temperature, set the MIX DSGN to match the boiler operating aquastat’s
setpoint temperature.
D. OUTDR DSGN (Outdoor Design)When the outdoor reset feature is selected, this setting represents the typical coldest
temperature of the year in the area where the installation is located. If this value is unknown, use the temperature value found
in ASHRAE Fundamentals for the area closest to the installation.