Isolate the problem between the control and the system. Now that the sequence of operation is known and
the system is sketched, is the control operating the proper pumps and valves at the correct times? Is the
control receiving the correct signals from the system as to when it should be operating? Are the proper
items selected in the menus of the control for the device that is to be operated?
Test the contacts, voltages and sensors. Using a multimeter, ensure that the control is receiving adequate
voltage to the power terminals and the demand terminals as noted in the technical data. Use the
multimeter to determine if the internal contacts on the control are opening and closing correctly. Follow
the instructions in the Testing the Wiring section to simulate closed contacts on the terminal blocks as
required. Test the sensors and their wiring as described in the Test the Sensors section.
Isolate the
Problem
Test the Contacts,
Voltages and
Sensors
The control was unable to read a piece of information from its EEPROM. This error can be caused by
a noisy power source. The control will load the factory defaults and continue operation if possible. All
settings in the Adjust menu must be reviewed before the error will clear.
The control is no longer able to read the boiler sensor due to a short circuit. The control will continue
to enable the boiler and will operate the diverting valve at 30% output while there is a heat demand
and until the sensor problem is repaired. The control will also record the time without the boiler return
sensor. Locate and repair the problem as described in the Test the Sensors section. To clear the error
message from the control after the sensor has been repaired, press the Item button.
The control is no longer able to read the boiler sensor due to an open circuit. The control will continue
to enable the boiler and will operate the diverting valve at 30% output while there is a heat demand
and until the sensor problem is repaired. The control will also record the time without the boiler return
sensor. Locate and repair the problem as described in the Test the Sensors section. To clear the error
message from the control after the sensor has been repaired, press the Item button.
The control is no longer able to read the mix supply sensor due to a short circuit. In this case the control
will operate the diverting valve at 30% output as long as there is a heat demand and until the sensor
problem is repaired. Locate and repair the problem as described in the Test the Sensors section. To
clear the error message from the control after the sensor has been repaired, press the Item button.
The control is no longer able to read the mix supply sensor due to an open circuit. In this case the
control will operate the diverting valve at 30% output as long as there is a heat demand and until
the sensor problem is repaired. Locate and repair the problem as described in the Test the Sensors
section. To clear the error message from the control after the sensor has been repaired, press the Item
button. Note: If a diverting valve is not installed, set the outdoor design (OUTDR DSGN) setting to
OFF, power off the control and then re-power.
The control is no longer able to read the outdoor sensor due to a short circuit. In this case the control
targets the design mix supply temperature and continues operation. Locate and repair the problem as
described in the Test the Sensors section. To clear the error message from the control after the sensor
has been repaired, press the Item button.
The control is no longer able to read the outdoor sensor due to an open circuit. In this case the control
targets the design mix supply temperature and continues operation. Locate and repair the problem as
described in the Test the Sensors section. To clear the error message from the control after the sensor
has been repaired, press the Item button. Note: If a diverting valve is operated as a setpoint control,
set the outdoor design (OUTDR DSGN) setting to OFF.
Error Messages