
42 of 60
A9. 3-way Multiple Boiler RTC in Primary/Secondary - Heating and DHW using Indirect Water Heater on Primary Loop;
Using Sequencer with & without Outdoor Reset (Mechanical)
120 V (ac)
24 V (ac)
Class II
Transformer
264
Outdoor Sensor
(S4) 070
M
Z3
M
Z2
A1
P4
Boiler Return
Sensor
(S1) 071
P1
C1
M1
V1
V3
Boiler Return
Sensor
(S2) 071
P2
C2
M2
V2
V3
4D
Max
M
Z1
P3
R1
Indirect
DHW
Tank
RTC
RTC
S3
A1 = Indirect Hot Water Aquastat
C1,C2 = Diverting Valve Actuating Motor
M1,M2 = By-Pass Mix Point
P1,P2 = Boiler Circulator
P3 = System Pump (runs on call for heat)
P4 = Indirect Circulator
R1 = Relay
S1,S2 = Boiler Return Sensor
S3 = Mix Supply Senor 071
S4 = Outdoor Sensor 070
V1,V2 = 3-Way Diverting Valve
V3 = Ball Valve, Balancing Valve
Z1...Z3 = Zones
NOTES:
1) Install the boiler as indicated above for systems where return temperatures may be less than 135F and heating/DHW with an indi-
rect water heater.
2) The Outdoor Sensor (S4) and the Mix Supply Sensor (S3) are required when the Outdoor Reset feature is selected. An appropriate
sequencer must also be selected. The mix sensor must be installed 10 pipe diameters downstream of the system pump, in the primary
loop. The mix sensor must be secured to the surface of the pipe using a wire tie or similar device.
3) The by-pass piping, diverting valve and boiler circulator must be sized using the sizing charts found in Appendix B.
4) A domestic hot water priority could be used provided the diversion from the heating system loop does not impact the system
heater’s performance.
5) Closely spaced tees must connect the branch to the larger header. The Tee centerlines must be no greater than 4 times the larger
header pipe diameter.
6) The diverting valves, V1 & V2, must be no greater than 11 linear feet of pipe from the Return Sensor, S1 & S2.
7) There shall be a MINIMUM of 4 linear feet of pipe between the By-pass Mix Point, M1 & M2, and the Return Sensor, S1 & S2.
8) The balancing valves in the boiler return lines, V3, may be necessary in low head by-pass loop applications.
9) The indirect heater aquastat (A1) is a normally closed switch. Circuit breaks on temperature rise.
10) Expansion tanks, air scoops and other components left out for clarity.
11) Observe all applicable plumbing and electrical codes.
This diagram is for reference only. The installer or designer is responsible for the proper selection and design of the
system.
Commenti su questo manuale